This product is used for stripple insulation shielding of 10kV and below XLPE insulated cables. It is produced with domestic raw materials by kneader equipment.
It has excellent mechanical and stable processability performances.
Recommend to process with the PE extruder
No Item Unit Technical Requirements 1 Relative Density g/cm³ ≤1.20 2 Tensile Strength MPa ≥12 3 Elongation at Break % ≥200 4 20℃ Volume Resistivity Ω·cm ≤100 5 90℃ Volume Resistivity Ω·cm ≤1000 6 90℃ Volume Resistivity after air aging(100℃×168h) Ω·cm ≤1000 7 Air Aging Test / (135±2℃)×168h 8 Tensile Strength Variation After Aging % ±25 9 Elongation Variation After Aging % ±25 10 Hot Set Test / 200℃×0.2MPa×15min 11 Hot Elongation % ≤100 12 Permanent Deformation after Cooling (Set) % ≤15 13 Peel Strength 20℃ N/cm 10-30 14 Moisture Content ppm ≤800 Note: More specifications, please contact our sales staff.
Specifications
Payment & Delivery
- Payment Terms:
- Delivery Time:
- Shipping:
- Port of Loading:
- HS Code:
- Storage:
Technical Table 1
| Model | Machine Barrel Temperature | Molding Temperature |
| OW-YP(W)-10 | 70-110℃ | 110-118℃ |
Technical Table 2
| No | Item | Unit | Technical Requirements |
| 1 | Relative Density | g/cm³ | ≤1.20 |
| 2 | Tensile Strength | MPa | ≥12 |
| 3 | Elongation at Break | % | ≥200 |
| 4 | 20℃ Volume Resistivity | Ω·cm | ≤100 |
| 5 | 90℃ Volume Resistivity | Ω·cm | ≤1000 |
| 6 | 90℃ Volume Resistivity after air aging(100℃×168h) | Ω·cm | ≤1000 |
| 7 | Air Aging Test | / | (135±2℃)×168h |
| 8 | Tensile Strength Variation After Aging | % | ±25 |
| 9 | Elongation Variation After Aging | % | ±25 |
| 10 | Hot Set Test | / | 200℃×0.2MPa×15min |
| 11 | Hot Elongation | % | ≤100 |
| 12 | Permanent Deformation after Cooling (Set) | % | ≤15 |
| 13 | Peel Strength 20℃ | N/cm | 10-30 |
| 14 | Moisture Content | ppm | ≤800 |
| Note: More specifications, please contact our sales staff. | |||